Serving scalars

Verified · scalar_metadata.rs · demo_scalars.py · check docs_verify · docs-verify

The badge reports the whole docs-verify suite, not this chapter alone.

What you'll build

The same two PVs as Your first PV, but described properly: engineering units, display precision, a description, alarm limits, drive limits, and a monitor deadband.

This is the difference between a number and a reading.

Rust

#![allow(unused)]
fn main() {
    let temperature = Pv::ai("SIM:TEMPERATURE", 22.5)
        .units("degC")
        .prec(2)
        .desc("Sample block temperature")
        // lolo, low, high, hihi — MAJOR outside the outer pair,
        // MINOR outside the inner pair.
        .alarm_limits(0.0, 15.0, 30.0, 40.0)
        // Monitors stay quiet for changes smaller than this.
        .mdel(0.5);

    let setpoint = Pv::ao("SIM:SETPOINT", 25.0)
        .units("degC")
        .prec(1)
        .desc("Demanded temperature")
        .drive_limits(0.0, 100.0);

    // `scalar_out`/`scalar_in` pick the wire type from the `ScalarValue`
    // variant of `initial` — not from Rust's `u16`/`u8`, which have no
    // native `Pv<T>` handle of their own. This is the route to the eight
    // NTScalar types `ai`/`ao`/`bi`/`bo`/`longin`/`longout`/`string_in`/
    // `string_out` don't cover.
    let gain = Pv::<ScalarValue>::scalar_out("SIM:GAIN", ScalarValue::U16(1));
    let status = Pv::<ScalarValue>::scalar_in("SIM:STATUS", ScalarValue::U8(0));

    let server = PvaServer::serve([
        AnyPv::from(temperature.clone()),
        AnyPv::from(setpoint.clone()),
        AnyPv::from(gain.clone()),
        AnyPv::from(status.clone()),
    ])
    .build()
    .await;
}

Note what this is not using. PvaServer::builder().ai(name, value) takes a name and an initial value and nothing else — there is no .units() on the builder. Metadata is set through typed Pv<T> handles, then handed to PvaServer::serve([...]). If you need metadata in code, that is the route.

(The other route is a .db file, covered in Loading .db files.)

Python

temperature = spvirit.ai(
    "SIM:TEMPERATURE",
    22.5,
    units="degC",
    prec=2,
    desc="Sample block temperature",
    # lolo, low, high, hihi
    alarm_limits=(0.0, 15.0, 30.0, 40.0),
    # Monitors stay quiet for changes smaller than this.
    mdel=0.5,
)

setpoint = spvirit.ao(
    "SIM:SETPOINT",
    25.0,
    units="degC",
    prec=1,
    desc="Demanded temperature",
    drive_limits=(0.0, 100.0),
)

# `type=` picks the wire type by name (or alias, e.g. "u16"); `writable=True`
# serves the output flavor, `False` (default) the input flavor.
gain = spvirit.scalar("SIM:GAIN", 1, type="ushort", writable=True)
status = spvirit.scalar("SIM:STATUS", 0, type="byte")

server = spvirit.Server(pvs=[temperature, setpoint, gain, status])
server.run()

Python has no such split — spvirit.ai() takes all of it as keyword arguments, and spvirit.Server(pvs=[...]) serves the handles.

What to notice

Metadata rides with the value. A client reading SIM:TEMPERATURE gets degC and precision: 2 in the same message. That is the NTScalar display structure from Normative Types, and it is why a PVAccess GUI can label an axis without being told to.

Alarm limits are four numbers in one call, ordered outward-in: alarm_limits(lolo, low, high, hihi). Crossing low or high is MINOR; crossing lolo or hihi is MAJOR. Alarms goes into this.

Drive limits are advertised, not enforced. This one will catch you:

$ spput SIM:SETPOINT 500
SIM:SETPOINT OK

$ spget SIM:SETPOINT
SIM:SETPOINT 2026-08-04 10:00:31.426 500

drive_limits(0.0, 100.0) populates the NTScalar control structure so clients know the intended range — and that is all it does. Nothing in the server clamps a write. If out-of-range values must be rejected, reject them yourself in an on_put handler; see Reacting to writes.

MDEL and ADEL behave differently from the rest. They are written into the record's field table rather than the NT payload, which means they are the two pieces of metadata you can read back QSRV-style:

$ spget SIM:TEMPERATURE.MDEL
SIM:TEMPERATURE.MDEL 2026-08-04 10:02:48.038 0.5

$ spget SIM:TEMPERATURE.EGU
Error: Timeout("read header")

.EGU times out because there is no such channel. Field access serves the dbCommon fields plus whatever a parsed .db file contained — and units set in code goes into the payload, not the field table. The units are still there; you just have to read the whole PV to see them. This is the gap described in EPICS in 10 minutes.

Choosing the wire type

ai/ao/bi/bo/longin/longout/string_in/string_out (Rust) and ai/ao/bo/longin/longout/string_in/string_out (Python) each fix the NTScalar wire type to one of double, boolean, int or string. PVAccess defines twelve NTScalar value types in total — boolean, byte, short, int, long, their unsigned variants (ubyte, ushort, uint, ulong), float, double, and string — and reaching the other eight needs an explicit type selection.

Rust

#![allow(unused)]
fn main() {
    // `scalar_out`/`scalar_in` pick the wire type from the `ScalarValue`
    // variant of `initial` — not from Rust's `u16`/`u8`, which have no
    // native `Pv<T>` handle of their own. This is the route to the eight
    // NTScalar types `ai`/`ao`/`bi`/`bo`/`longin`/`longout`/`string_in`/
    // `string_out` don't cover.
    let gain = Pv::<ScalarValue>::scalar_out("SIM:GAIN", ScalarValue::U16(1));
    let status = Pv::<ScalarValue>::scalar_in("SIM:STATUS", ScalarValue::U8(0));
}

Pv::<ScalarValue>::scalar_out/scalar_in build a record whose wire type is whatever ScalarValue variant initial holds — scalar_out for a writable PV, scalar_in for read-only.

Python

# `type=` picks the wire type by name (or alias, e.g. "u16"); `writable=True`
# serves the output flavor, `False` (default) the input flavor.
gain = spvirit.scalar("SIM:GAIN", 1, type="ushort", writable=True)
status = spvirit.scalar("SIM:STATUS", 0, type="byte")

spvirit.scalar(name, initial, *, type, writable=False, **opts) picks the wire type by name (or alias, e.g. "u16"/"i32"); writable=True serves the output flavor. The full type-name/alias table and the value coercion rules (overflow, widening, narrowing) are in spvirit-py's README, NT scalar type coverage section — the same reference the Python API page points to for pv/scalar.

Run it

# Terminal 1
cargo run -p spvirit-server --example scalar_metadata
# or: python spvirit-py/examples/demo_scalars.py

# Terminal 2
spget SIM:TEMPERATURE
spget SIM:TEMPERATURE.MDEL
spput SIM:SETPOINT 30
spinfo SIM:GAIN
spinfo SIM:STATUS

Terminal 2 prints:

$ spget SIM:TEMPERATURE
SIM:TEMPERATURE 2026-08-06 09:13:06.435 22.5

$ spget SIM:TEMPERATURE.MDEL
SIM:TEMPERATURE.MDEL 2026-08-06 09:13:06.707 0.5

$ spput SIM:SETPOINT 30
SIM:SETPOINT OK

spinfo prints the type of every field. Only the third line differs between the two records — SIM:GAIN is a ushort, SIM:STATUS a ubyte — and the remaining forty-odd lines are the same NTScalar skeleton in both:

$ spinfo SIM:GAIN
SIM:GAIN:
struct epics:nt/NTScalar:1.0
value: ushort
alarm: structure
  severity: int
  status: int
  message: string
timeStamp: structure
  secondsPastEpoch: long
  nanoseconds: int
  userTag: int
display: structure
  limitLow: double
  limitHigh: double
  description: string
  units: string
  precision: int
  form: structure
    index: int
    choices: string[]
control: structure
  limitLow: double
  limitHigh: double
  minStep: double
valueAlarm: structure
  active: boolean
  lowAlarmLimit: double
  lowWarningLimit: double
  highWarningLimit: double
  highAlarmLimit: double
  lowAlarmSeverity: int
  lowWarningSeverity: int
  highWarningSeverity: int
  highAlarmSeverity: int
  hysteresis: ubyte

$ spinfo SIM:STATUS
SIM:STATUS:
struct epics:nt/NTScalar:1.0
value: ubyte
...

That is the point of the narrow types: the wire carries two bytes for a ushort and one for a ubyte, but the surrounding structure — alarm, timestamp, display, control, valueAlarm — is identical whatever the value type is.

Next

Reading and writing.